You are here: Hardware Setup > Assa Aperio Lock Setup

Basic ASSA Aperio Configuration

Doors.NET provides support for several Assa Abloy wireless locks featuring Aperio technology and both wireless and wired IP Locks. These locks can be used with or without hard-wired Keri controller-managed doors on the same system, providing you with the utmost in deployment flexibility. The Aperio locks are only supported with the NXT-MSC (Mercury Powered 2 or 4 door controllers).

 

Aperio is the smart technology that enables mechanical locks to be wirelessly linked to an existing access control system. The heart of Aperio is a short-distance, wireless communication protocol, designed to link with an online electronic access system with an Aperio enabled mechanical lock.


Aperio Locks

 

 

Each lock requires a hub for its wireless link, the hub connects into a bus of an Mercury-Powered NXT controller. Each controller can manage up to 16 Aperio hubs/locks.

 



This section provides information regarding the setup process in Doors.NET, adding the relevant lock or hub type, and addressing information for the hub.

 

Installers and integrators who wish to use the Aperio range of products with Doors.NET MUST be certified by ASSA Abloy. Keri Systems DOES NOT supply or support the software application which is required to configure the wireless locks. Keri Systems recommends that you contact your local ASSA Abloy supplier for further details about product training and support.

 

Requirements

 

Limitations

 

Supported Aperio Devices

The Aperio ribbon bar displays the supported wireless locking devices and the AH30 hub.

 

 

Communication Hubs

Doors.NET supports both the AH-15 and the AH-30 hubs. The AH-15 hub pairs directly with a single Aperio wireless lock. The AH-30 hub is capable of supporting up to 8 Aperio locks. Multiple hubs can be connected to a single NXT reader port, covering a maximum of 16 locks per controller.

 

 

Installing the Hub

Connecting the hub to the NXT Mercury Powered controller using the RS-485 interface is the default method. It is the same wiring for the AH-15 and the AH-30.

 

There is an 8-pin terminal block on the reverse of the hub for making the wiring connections to the controller.

 

 

RS-485 Wiring to NXT Mercury Powered Controller

 

Aperio Hub Wiring

 

Wiegand Wiring to NXT Mercury Powered Controller

 

When connecting to the controller via Wiegand you must have a Reader Interface Module (RIM) plugged into the controller’s reader port and it needs to be configured for Wiegand (Refer to the RIM Installation guide for setup instructions. The hub is wired into the 8-pin terminal block connected to the RIM.

Aperio Wiring- Wiegand

 

Dip Switch Setting:

• Switch 10 - Antenna set to INT not EXT


Set Comm Address

 

 

Adding to the NXT Mercury Powered Controller

Highlight the controller’s bus in the hardware tree and select from the Aperio ribbon the device(s) you wish to add.

 

 

NOTE: If the Aperio icons are not available, please refer to License Manager permissions to ensure that your system is enabled for Aperio.

 

Addressing the Hub

The address of the hub is determined by Doors.NET. Refer to the Comm Address field in the hub properties to determine the device address for the hub.

 

 

This addressing follows a specific pattern depending upon the types of hubs being installed. Refer to the table below appropriate to your installation.

 

Addressing for Two 8-Port Hubs (AH-30)

 

Bus Number First Hub Address Second Hub Address
1 1 5
2 2 6
3 3 7
4 4 8

 

Addressing for One AH-30 8-Port Hub (AH-30)

and Eight AH-15 1-Port Hubs (AH-15)

 

Bus Number 8-Port Hub 1-Port Hub 1 1-Port Hub 2 1-Port Hub 3 1-Port Hub 4 1-Port Hub 5 1-Port Hub 6 1-Port Hub 7 1-Port Hub 8
1 5 9 13 17 18 19 20 21 22
2 6 10 14 17 18 19 20 21 22
3 7 11 15 17 18 19 20 21 22
4 8 12 16 17 18 19 20 21 22

 

Addressing for Eight 1-Port Hubs (AH-15)

and One 8-Port Hub (AH-30)

 

Bus Number 8-Port Hub 1-Port Hub 1 1-Port Hub 2 1-Port Hub 3 1-Port Hub 4 1-Port Hub 5 1-Port Hub 6 1-Port Hub 7 1-Port Hub 8
1 1 23 24 25 26 27 28 29 30
2 2 23 24 25 26 27 28 29 30
3 3 23 24 25 26 27 28 29 30
4 4 23 24 25 26 27 28 29 30

 

NOTE: Once the hub has been added to an NXT-MSC controller you MUST perform a RAM reset. The controller will re-configure the RS-485 protocol for Aperio devices. Only other Aperio devices can be used on that bus; no other peripheral type will be accepted.

 

Setting the Address on the Hub

There are 30 available address numbers for the hubs, set via the DIP switch on each hub. For example, Switch 1 in the UP position and all others DOWN will set the unit to address 1. All 30 address switch positions are shown in the figure below.